EX Dual Fuel Steam Boilers
				
    
        
            
                
                    
                        
                            The Miura EX Gas/Oil Series Industrial Steam Boiler is the most versatile industrial steam boiler in the world.                        
                        
                       
                            The Miura EX Series steam boilers, with gas and oil fuel options, are ideal for hospitals and other facilities that are required to have a secondary fuel source.
The EX steam boiler uses our floating header design on an upright drum-shaped pressure vessel. With a single button, the Miura EX-Series boiler a from a cold start to full steam output in less than 5 minutes. These quick start-up benefits enable many industries to consume less fuel and boiler water, reducing emissions and operating cost.
- Dual fuel: Natural Gas, Propane or #2 Fuel Oil
- High-pressure available (300 MAWP, 250 MAWP or 170 MAWP)
- NOx rating is available as low as 30ppm depending on model
- Quick start up in just 5 minutes
- Occupies 33% less floor space than typical firetube boilers
- Equipped with an early warning scale monitor
 
                        	
                        
                        
                        
                     
                 
                
                    
                
             
        
            
                
                    
                        
                            Features                        
                        
                       
                            The unique compact design of the Miura EX Series steam boiler uses a low water volume pressure vessel offering high output capacities to meet your facilities demands. The reduced boiler footprint provides design flexibility, reduced construction cost, and better utilization of existing space to increase steam capabilities. The “brain” of the EX-Series, the BL Controller, provides online boiler monitoring  and measuring capabilities on an easy-to-read LCD display and enhances boiler maintenance procedures with data-driven alerts. The BL Controller monitors:
- Steam Pressure
- Flue Gas Temperature
- Feed Water Temperature
- Scale Monitor Temperature
- Overheat Monitor Temperature
- Flame Current
- Remaining Time to Blowdown
- Water Conductivity
- Plus much more!
 
                        
                     
                 
                
                    
                
             
                
        
    
        
                           Contact a Miura Rep
                Learn more about our EX boilers.
            
                     
        
     
 
                
            
     
    
    Standard Pressure
    
        
            
                
                 
                
                Utilization Horsepower
                Maximum Pressure [1]
                Equivalent Output [2]
                Heat Output
                Efficiency (fuel to stream) [3]
                Operational Weight
                Operational Water Content
                 Shipping Weight
                Width
                Length
                Height
                Power Supply
                Fuel Type [4] 
                No. 2 Oil
                Gas Supply Pressure
                Chimney Diameter (ID)
             
            
                UNIT
                 
                
                BHP
                PSIG
                LB/HR
                MMBTU/HR
                 
                LBS
                 
                LBS
                IN.
                IN.
                IN.
                 
                 
                GAL/HR
                PSIG
                IN.
             
            
                
                    
                     
                    100
                    170
                    3,450
                    3.348
                    85%
                    5,900
                    65
                    4,600
                    80 1/8"
                    108 1/2"
                    98 7/8"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    27.5
                    3-5 PSIG
                    14" OD
                 
            
                
                    
                     
                    150
                    170
                    5,175
                    5.022
                    85%
                    9,600
                    90
                    7,800
                    68 1/2"
                    130"
                    119 5/8"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    41.2
                    3-5 PSIG
                    20" OD
                 
            
                
                    
                     
                    200
                    170
                    6,900
                    6.695
                    85%
                    9,600
                    90
                    7,800
                    68 1/2"
                    130"
                    119 5/8"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    55
                    3-5 PSIG
                    20" OD
                 
            
                
                    
                     
                    250
                    170
                    8,625
                    8.369
                    85%
                    9,900
                    110
                    8,000
                    68 1/2"
                    135 1/8"
                    145 1/4"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    68,7
                    3-5 PSIG
                    20" OD
                 
            
                
                    
                     
                    300
                    170
                    10,350
                    10.043
                    85%
                    13,500
                    135
                    11,200
                    76 3/4"
                    141 3/4"
                    156 1/8"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    85.5
                    3-5 PSIG
                    26" OD
                 
            
            
         
     
	        
							                
					Note 1: Optional EXH-SGO Series at 250 Psig MAWP, 225 Psig maximum operating.                
							                
					Note 2: Equivalent output calculated from and at 212ºF (100ºC) feed water at 212ºF (100ºC) steam.                
							                
					Note 3: Thermal effieciencies are based on high heating values of fuels at 68ºF (20ºC) feed water.                
							                
					Note 4: UL and c-UL approved for natural gas or propane.                
			         
	    Low Nox Burner with FGR
    
        
            
                
                 
                
                Utilization Horsepower
                Maximum Pressure [1]
                Equivalent Output [2]
                Heat Output
                Efficiency (fuel to stream) [3]
                Operational Weight
                Operational Water Content
                 Shipping Weight
                Width
                Length
                Height
                Power Supply
                Fuel Type [4] 
                No. 2 Oil
                Gas Supply Pressure
                Chimney Diameter (ID)
             
            
                UNIT
                 
                
                BHP
                PSIG
                LB/HR
                MMBTU/HR
                 
                LBS
                 
                LBS
                IN.
                IN.
                IN.
                 
                 
                GAL/HR
                PSIG
                IN.
             
            
                
                    
                     
                    250
                    170
                    8,625
                    8.369
                    85%
                    13,700
                    135
                    11,200
                    76 3/4"
                    140 1/2"
                    156 1/8"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    68.7
                    3-5 PSIG
                    26" OD
                 
            
                
                    
                     
                    300
                    170
                    10,350
                    10.043
                    85%
                    13,700
                    135
                    11,200
                    76 3/4"
                    140 1/2"
                    156 1/8"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    82.5
                    3-5 PSIG
                    26" OD
                 
            
            
         
     
	        
							                
					Note 1: Optional EXH-SGO Series at 250 Psig MAWP, 225 Psig maximum operating.                
							                
					Note 2: Equivalent output calculated from and at 212ºF (100ºC) feed water at 212ºF (100ºC) steam.                
							                
					Note 3: Thermal effieciencies are based on high heating values of fuels at 68ºF (20ºC) feed water.                
							                
					Note 4: UL and c-UL approved for natural gas or propane.                
			         
	    High Pressure
    
        
            
                
                 
                
                Utilization Horsepower
                Maximum Pressure [1]
                Equivalent Output [2]
                Heat Output
                Efficiency (fuel to stream) [3]
                Operational Weight
                Operational Water Content
                 Shipping Weight
                Width
                Length
                Height
                Power Supply
                Fuel Type [4] 
                No. 2 Oil
                Gas Supply Pressure
                Chimney Diameter (ID)
             
            
                UNIT
                 
                
                BHP
                PSIG
                LB/HR
                MMBTU/HR
                 
                LBS
                 
                LBS
                IN.
                IN.
                IN.
                 
                 
                GAL/HR
                PSIG
                IN.
             
            
                
                    
                     
                    170 - 270
                    300
                    6,900
                    6.695
                    84%
                    10,500
                    95
                    8,500
                    68 1/2"
                    130"
                    119 5/8"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    55.6
                    3-5 PSIG
                    20" OD
                 
            
                
                    
                     
                    300
                    300
                    10,350
                    10.043
                    84%
                    15,100
                    140
                    12,400
                    76 3/4"
                    141 3/4"
                    156 1/8"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    83.4
                    3-5 PSIG
                    26" OD
                 
            
            
         
     
	        
							                
					Note 1: Optional EXH-SGO Series at 250 Psig MAWP, 225 Psig maximum operating.                
							                
					Note 2: Equivalent output calculated from and at 212ºF (100ºC) feed water at 212ºF (100ºC) steam.                
							                
					Note 3: Thermal effieciencies are based on high heating values of fuels at 68ºF (20ºC) feed water.                
							                
					Note 4: UL and c-UL approved for natural gas or propane.                
			         
	    High Pressure / Low Nox Burner with FGR
    
        
            
                
                 
                
                Utilization Horsepower
                Maximum Pressure [1]
                Equivalent Output [2]
                Heat Output
                Efficiency (fuel to stream) [3]
                Operational Weight
                Operational Water Content
                 Shipping Weight
                Width
                Length
                Height
                Power Supply
                Fuel Type [4] 
                No. 2 Oil
                Gas Supply Pressure
                Chimney Diameter (ID)
             
            
                UNIT
                 
                
                BHP
                PSIG
                LB/HR
                MMBTU/HR
                 
                LBS
                 
                LBS
                IN.
                IN.
                IN.
                 
                 
                GAL/HR
                PSIG
                IN.
             
            
                
                    
                     
                    300
                    300
                    10,350
                    10.043
                    84%
                    15,300
                    40
                    12,400
                    76 3/4"
                    141 3/4"
                    156 1/8"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    83.4
                    3-5 PSIG
                    26" OD
                 
            
                
                    
                     
                    250
                    250
                    8,265
                    8.369
                    84%
                    15,300
                    140
                    12,400
                    76 3/4"
                    141 3/4"
                    156 1/8"
                    575,460,380,230 OR 208 Volts, 3 Phase, 60Hz
                    Natural Gas, Propane, No. 2 Oil
                    69.5
                    3-5 PSIG
                    26" OD
                 
            
            
         
     
	        
							                
					Note 1: Optional EXH-SGO Series at 250 Psig MAWP, 225 Psig maximum operating.                
							                
					Note 2: Equivalent output calculated from and at 212ºF (100ºC) feed water at 212ºF (100ºC) steam.                
							                
					Note 3: Thermal effieciencies are based on high heating values of fuels at 68ºF (20ºC) feed water.                
							                
					Note 4: UL and c-UL approved for natural gas or propane.